Heater & Air Conditioning System. Lexus Gs430, Gs300. Uzs190 Grs190
Air Conditioning. Lexus Gs430, Gs300. Uzs190 Grs190
Room Temperature Sensor -- Inspection |
1. INSPECT ROOM TEMPERATURE SENSOR |
Remove the A/C room temperature sensor.
![]() |
Disconnect the connector from the A/C room temperature sensor.
Measure the resistance according to the value(s) in the table below.
- Standard resistance:
Tester Connection Condition Specified Condition 1 (+) - 2 (-) 10°C (50°F) 3.00 to 3.73 kΩ 1 (+) - 2 (-) 15°C (59°F) 2.45 to 2.88 kΩ 1 (+) - 2 (-) 20°C (68°F) 1.95 to 2.30 kΩ 1 (+) - 2 (-) 25°C (77°F) 1.60 to 1.80 kΩ 1 (+) - 2 (-) 30°C (86°F) 1.28 to 1.47 kΩ 1 (+) - 2 (-) 35°C (95°F) 1.00 to 1.22 kΩ 1 (+) - 2 (-) 40°C (104°F) 0.80 to 1.00 kΩ 1 (+) - 2 (-) 45°C (113°F) 0.65 to 0.85 kΩ 1 (+) - 2 (-) 50°C (122°F) 0.50 to 0.70 kΩ 1 (+) - 2 (-) 55°C (131°F) 0.44 to 0.60 kΩ 1 (+) - 2 (-) 60°C (140°F) 0.36 to 0.50 kΩ
- NOTICE:
- Even slightly touching the sensor may change the resistance value. Be sure to hold the connector of the sensor.
- When measuring, the sensor temperature must be the same as the ambient temperature.
- HINT:
- As the temperature increases, the resistance decreases (see the graph).