Air Conditioning System (For Automatic Air Conditioning System) Data List / Active Test

Vehicle Interior. Land Cruiser. Urj200, 202 Grj200 Vdj200
Heating Air Conditioning. Land Cruiser. Urj200, 202 Grj200 Vdj200
  1. DATA LIST

  1. ACTIVE TEST

Air Conditioning System (For Automatic Air Conditioning System) -- Data List / Active Test


HINT:
Using the intelligent tester to read the Data List allows the values or states of switches, sensors, actuators and other items to be read without removing any parts. This non-intrusive inspection can be very useful because intermittent conditions or signals may be discovered before parts or wiring is disturbed. Reading the Data List information early in troubleshooting is one way to save diagnostic time.
NOTICE:
In the table below, the values listed under "Normal Condition" are reference values. Do not depend solely on these reference values when deciding whether a part is faulty or not.

DATA LIST
  1. Connect the intelligent tester to the DLC3.

  2. Turn the engine switch on (IG).

  3. Turn the intelligent tester on.

  4. Enter the following menus: Body / Air Conditioner / Data List.

  5. Enter the following menus: Powertrain / Engine and ECT / Data List.

  6. According to the display on the intelligent tester, read the Data List.

    Air Conditioner
    Tester Display
    Measurement Item/Range
    Normal Condition
    Diagnostic Note
    Room Temperature Sensor
    Front room temperature sensor /
    Min.: -6.5°C (20.3°F)
    Max.: 57.25°C (135.05°F)
    Actual room temperature for front seat displayed
    Open in the circuit: -6.5°C (20.3°F).
    Short in the circuit: 57.25°C (135.05°F).
    Ambient Temp Sensor
    Ambient temperature sensor /
    Min.: -23.3°C (-9.94°F)
    Max.: 65.95°C (150.71°F)
    Actual ambient temperature displayed
    Open in the circuit: -23.3°C (-9.94°F).
    Short in the circuit: 65.95°C (150.71°F).
    Adjusted Ambient Temp
    Adjusted ambient temperature /
    Min.: -30.8°C (-23.44°F)
    Max.: 50.8°C (123.44°F)
    Adjusted ambient temperature displayed
    -
    Evaporator Fin Thermistor
    No. 1 cooler thermistor /
    Min.: -29.7°C (-21.46°F)
    Max.: 59.55°C (139.19°F)
    Actual evaporator temperature displayed
    Open in the circuit: -29.7°C (-21.46°F).
    Short in the circuit: 59.55°C (139.19°F).
    Evaporator Target Temp
    Target evaporator temperature /
    Min.: 1.5°C (34.7°F)
    Max.: 4.0°C (39.2°F)
    Target evaporator temperature displayed
    -
    Solar Sensor (D Side)
    Driver side solar sensor /
    Min.: 0, Max.: 255
    Driver side solar sensor voltage increases as brightness increases
    Open in the circuit: 0
    Short in the circuit: 255
    Solar Sensor (P Side)
    Passenger side solar sensor /
    Min.: 0, Max.: 255
    Passenger side solar sensor voltage increases as brightness increases
    Open in the circuit: 0
    Short in the circuit: 255
    Engine Coolant Temp
    Engine coolant temperature /
    Min.: 1.3°C (34.34°F)
    Max.: 90.55°C (194.99°F)
    Actual engine coolant temperature displayed while engine warmed up
    -
    Set Temperature (D Side)
    Driver side set temperature /
    MAX COLD: 15.5°C (59.9°F)
    MAX HOT: 32.5°C (90.5°F)
    Driver side actual set temperature displayed
    -
    Set Temperature (P Side)
    Passenger side set temperature /
    MAX COLD: 15.5°C (59.9°F)
    MAX HOT: 32.5°C (90.5°F)
    Passenger side actual set temperature displayed
    -
    A/M Servo Targ Pulse (Rear D)
    Rear air mix damper servo motor target pulse /
    Min.: 9, Max.: 54 (for LHD)
    Min.: 8, Max.: 53 (for RHD)
    for LHD
    1. MAX COOL: 9 (pulse)
    2. MAX HOT: 54 (pulse)
    for RHD
    1. MAX COOL: 53 (pulse)
    2. MAX HOT: 8 (pulse)
    -
    A/M Servo Targ Pulse (Rear P)
    Rear air mix damper servo motor (for front passenger side) target pulse /
    Min.: 8, Max.: 53 (for LHD)
    Min.: 9, Max.: 54 (for RHD)
    for LHD
    1. MAX COOL: 53 (pulse)
    2. MAX HOT: 8 (pulse)
    for RHD
    1. MAX COOL: 9 (pulse)
    2. MAX HOT: 54 (pulse)
    -
    Hand Free Telephone
    Handsfree telephone / OFF or ON
    ON: Handsfree telephone used
    OFF: Handsfree telephone not used
    -
    Blower Motor Speed Level
    Blower motor speed level /
    Min.: 0 level,
    Max.: 31 level
    Increases in range between 0 and 31 as blower motor speed increases
    -
    Regulator Pressure Sensor
    Refrigerant pressure sensor /
    Min.: -0.4566 MPaG
    Max.: 3.2943 MPaG
    Actual refrigerant pressure displayed
    -
    Room Temp Sensor (Rear)
    Rear room temperature sensor /
    Min.: -6.5°C (20.3°F)
    Max.: 57.25°C (135.05°F)
    Actual rear room temperature displayed
    Open in the circuit: -6.5°C (20.3°F).
    Short in the circuit: 57.25°C (135.05°F).
    Ambient Temp Sens (Rear)
    No. 2 cooler thermistor /
    Min.: -29.7°C (-21.46°F)
    Max.: 59.55°C (139.19°F)
    Actual rear evaporator temperature displayed
    Open in the circuit: -29.7°C (-21.46°F).
    Short in the circuit: 59.55°C (139.19°F).
    Blower Motor Level (Rear)
    Rear blower motor speed level /
    Min.: 0, Max.: 31
    Increases in range between 0 to 31 as rear blower motor speed increases
    -
    Air Mix Servo Targ Pulse(D)
    Air mix damper servo motor (for driver side) target pulse /
    Min.: 8, Max.: 90 (for LHD)
    Min.: 8, Max.: 90 (for RHD)
    for LHD
    1. MAX COOL: 90 (pulse)
    2. MAX HOT: 8 (pulse)
    for RHD
    1. MAX COOL: 8 (pulse)
    2. MAX HOT: 90 (pulse)
    -
    Air Mix Servo Targ Pulse(P)
    Air mix damper servo motor (for front passenger side) target pulse /
    Min.: 8, Max.: 90 (for LHD)
    Min.: 8, Max.: 90 (for RHD)
    for LHD
    1. MAX COOL: 8 (pulse)
    2. MAX HOT: 90 (pulse)
    for RHD
    1. MAX COOL: 90 (pulse)
    2. MAX HOT: 8 (pulse)
    -
    Air Inlet Damper Targ Pulse
    REC/FRS damper servo motor target pulse /
    Min.: 9, Max.: 37
    for LHD
    Recirculation: 37 (pulse)
    Fresh: 9 (pulse)
    for RHD
    Recirculation: 9 (pulse)
    Fresh: 37 (pulse)
    -
    Cool Air Bypass Pulse
    Cool air bypass damper servo motor target pulse /
    Min.: 6, Max.: 57
    Shut: 6 (pulse)
    Open: 57 (pulse)
    -
    Electric Heater Count
    Electric heater count /
    Min.: 0, Max.: 3
    -
    -
    Shift Set Temperature
    Shift set temperature / +2 C, +1 C, NORMAL, -1 C, -2 C
    Customized value displayed
    -
    Air Inlet Mode
    Air inlet mode / AUTO, MANUAL
    Customized value displayed
    -
    Compressor Mode
    Compressor mode / AUTO, MANUAL
    Customized value displayed
    -
    Compressor/DEF Mode
    Compressor/DEF mode / LINK, NORMAL
    Customized value displayed
    -
    Evaporator Control
    Evaporator control / AUTO, MANUAL
    Customized value displayed
    -
    Button Press Buzzer
    Button press buzzer / ON or OFF
    Customized value displayed
    -
    Foot/DEF Auto Mode
    FOOT/DEF auto mode / ON or OFF
    Customized value displayed
    -
    Foot/DEF Auto Blow Up
    FOOT/DEF auto blower up function / ON or OFF
    Customized value displayed
    -
    Filter Sensor
    Filter sensor / LESS, NORMAL, MORE
    Customized value displayed
    -
    Rear A/P HI Set
    Rear A/P HI set / ON or OFF
    Customized value displayed
    -
    Ambient Temperature Shift
    Ambient temperature shift / +3 C, +2 C, +1 C, NORMAL, -1 C, -2 C, -3 C
    Customized value displayed
    -
    A/O Damper FACE Pos(D)
    Air outlet damper servo motor (for driver side mode) target pulse /
    Min.: 6, Max.: 117
    FACE1: 117 (pulse)
    FACE2: 109 (pulse)
    B/L1: 93 (pulse)
    B/L2: 81 (pulse)
    FOOT-F: 41 (pulse)
    FOOT-R: 41 (pulse)
    FOOT-D: 52 (pulse)
    F/D: 18 (pulse)
    DEF: 6 (pulse)
    -
    A/O Damper FACE Pos(P)
    Air outlet damper servo motor (for front passenger side mode) target pulse /
    Min.: 6, Max.: 117 (for LHD)
    Min.: 9, Max.: 120 (for RHD)
    for LHD
    1. FACE1: 117 (pulse)
    2. FACE2: 109 (pulse)
    3. B/L1: 93 (pulse)
    4. B/L2: 81 (pulse)
    5. FOOT-F: 41 (pulse)
    6. FOOT-R: 41 (pulse)
    7. FOOT-D: 52 (pulse)
    8. F/D: 18 (pulse)
    9. DEF: 6 (pulse)
    for RHD
    1. FACE1: 9 (pulse)
    2. FACE2: 17 (pulse)
    3. B/L1: 33 (pulse)
    4. B/L2: 45 (pulse)
    5. FOOT-F: 85 (pulse)
    6. FOOT-R: 85 (pulse)
    7. FOOT-D: 74 (pulse)
    8. F/D: 108 (pulse)
    9. DEF: 120 (pulse)
    -
    Air Mix Servo Targ Pls(F&R D)
    Front air mix damper servo motor (for driver side rear air flow) target pulse /
    Min.: 13, Max.: 41 (for LHD)
    Min.: 5, Max.: 33 (for RHD)
    for LHD
    1. MAX COOL: 13 (pulse)
    2. MAX HOT: 41 (pulse)
    for RHD
    1. MAX COOL: 33 (pulse)
    2. MAX HOT: 5 (pulse)
    -
    Air Mix Servo Targ Pls(F&R P)
    Front air mix damper servo motor (for front passenger side rear air flow) target pulse /
    Min.: 5, Max.: 33 (for LHD)
    Min.: 13, Max.: 41 (for RHD)
    for LHD
    1. MAX COOL: 33 (pulse)
    2. MAX HOT: 5 (pulse)
    for RHD
    1. MAX COOL: 13 (pulse)
    2. MAX HOT: 41 (pulse)
    -
    Air Outlet Servo Pls (F&R D)
    Air outlet damper servo motor (for rear seat mode) target pulse /
    Min.: 9, Max.: 79
    FACE1: 9 (pulse)
    B/L1: 28 (pulse)
    FOOT-O: 41 (pulse)
    F/D: 67 (pulse)
    DEF: 79 (pulse)
    -
    Air Outlet Servo Pulse (R)
    Rear air outlet damper servo motor target pulse /
    Min.: 7, Max.: 83
    FOOT: 7 (pulse)
    B/L: 42 (pulse)
    FACE: 83 (pulse)
    -
    Room Temperature Sensor (RP)
    Rear room temperature sensor /
    Min.: -6.5°C (20.3°F)
    Max.: 57.25°C (135.05°F)
    Actual rear room temperature displayed
    Open in the circuit: -6.5°C (20.3°F)
    Short in the circuit: 57.25°C (135.05°F)
    Set Temperature (Rear D side)
    Rear driver side set temperature /
    MAX COLD: 0°C (32°F)
    MAX HOT: 32°C (54°F)
    Rear driver side actual set temperature displayed
    -
    Set Temperature (Rear P side)
    Rear passenger side set temperature /
    MAX COLD: 0°C (32°F)
    MAX HOT: 32°C (54°F)
    Rear passenger side actual set temperature displayed
    -
    Foot Duct Sensor(Rear D)
    Min.: -12.7°C (9.14°F)
    Max.: 76.55°C (169.79°F)
    Actual air duct temperature sensor (for driver side) displayed
    Open in the circuit: -12.7°C (9.14°F)
    Short in the circuit: 76.55°C (169.79°F)
    Foot Duct Sensor(Rear P)
    Min.: -12.7°C (9.14°F)
    Max.: 76.55°C (169.79°F)
    Actual air duct temperature sensor (for passenger side) displayed
    Open in the circuit: -12.7°C (9.14°F)
    Short in the circuit: 76.55°C (169.79°F)
    Number of Trouble Codes
    Number of trouble codes /
    Min.: 0, Max.: 255
    Number of DTCs displayed
    -
    A/O Damper FOOT/DEF Pos(P)
    Air outlet damper servo motor (for DEF mode) target pulse /
    Min.: 6, Max.: 117
    1. FACE1: 117 (pulse)
    2. FACE2: 109 (pulse)
    3. B/L1: 93 (pulse)
    4. B/L2: 81 (pulse)
    5. FOOT-D: 52 (pulse)
    6. FOOT-R: 41 (pulse)
    7. FOOT-F: 41 (pulse)
    8. F/D: 18 (pulse)
    9. DEF: 6 (pulse)
    -

    Engine
    Tester Display
    Measurement Item/Range
    Normal Condition
    Diagnostic Note
    A/C Signal
    A/C signal / ON or OFF
    ON: A/C Switch on
    OFF: A/C Switch off
    -


ACTIVE TEST
HINT:
Using the intelligent tester to perform Active Tests allows relays, VSVs, actuators and other items to be operated without removing any parts. This non-intrusive functional inspection can be very useful because intermittent operation may be discovered before parts or wiring is disturbed. Performing Active Tests early in troubleshooting is one way to save diagnostic time. Data List information can be displayed while performing Active Tests.
  1. Connect the intelligent tester to the DLC3.

  2. Turn the engine switch on (IG).

  3. Turn the intelligent tester on.

  4. Enter the following menus: Body / Air Conditioner / Active Test.

  5. According to the display on the intelligent tester, perform the Active Test.

    Tester Display
    Test Part
    Control Range
    Diagnostic Note
    Blower Motor
    Front blower motor
    Min.: 0, Max.: 31
    -
    Magnetic Clutch Relay
    Magnetic clutch relay
    OFF or ON
    -
    Air Mix Servo Targ Pulse(D)
    Air mix servo motor pulse (Front A/C D side)
    Min.: 8, Max.: 90
    -
    Air Mix Servo Targ Pulse(P)
    Air mix servo motor pulse (Front A/C P side)
    Min.: 8, Max.: 90
    -
    Air Inlet Damper Targ Pulse
    Air inlet damper target pulse
    Min.: 9, Max.: 37
    -
    Cool Air Bypass Pulse
    Driver side cool air bypass pulse
    Min.: 6, Max.: 57
    -
    Rear Blower Motor
    Rear blower motor
    Min.: 0, Max.: 31
    -
    Rear Air Mix Servo Targ Pulse
    Rear air mix damper servo motor pulse
    for LHD
    Min.: 9, Max.: 54
    for RHD
    Min.: 8, Max.: 53
    -
    DEF A/O Servo Pulse(D)
    Rear air outlet damper servo motor pulse
    Min.: 7, Max.: 83
    -
    Rear A/M Servo Pulse(P)
    Rear air mix damper servo motor (for front passenger side) pulse
    for LHD
    Min.: 8, Max.: 53
    for RHD
    Min.: 9, Max.: 54
    -
    Rear A/C Mag Valve
    Rear A/C magnetic valve
    OFF or ON
    -
    Face A/O Servo Pulse(D)
    Air outlet servo motor pulse (D side)
    Min.: 6, Max.: 117
    -
    Face A/O Servo Pulse(P)
    Air outlet servo motor pulse (P side)
    for LHD
    Min.: 6, Max.: 117
    for RHD
    Min.: 9, Max.: 120
    -
    A/M Servo Puls(F&R D)
    Air mix servo motor pulse (Front A/C rear air flow D side)
    for LHD
    Min.: 9, Max.: 54
    for RHD
    Min.: 8, Max.: 53
    -
    A/M Servo Puls(F&R P)
    Air mix servo motor pulse (Front A/C rear air flow P side)
    for LHD
    Min.: 8, Max.: 53
    for RHD
    Min.: 9, Max.: 54
    -
    A/O Servo Pulse(F&R D)
    Air outlet servo motor pulse (Front A/C rear air flow D side)
    Min.: 9, Max.: 79
    -
    A/O Servo Pulse(Rr D)
    Air outlet servo motor pulse (Rr D side)
    Min.: 7, Max.: 83
    -