Front Evaporator Temperature Sensor -- Inspection |
1. INSPECT NO. 1 COOLER THERMISTOR |
![]() |
Measure the resistance according to the value(s) in the table below.
- Standard Resistance:
Tester Connection Condition Specified Condition 1 - 2 -10°C (14°F) 7.30 to 9.10 kΩ -5°C (23°F) 5.65 to 6.95 kΩ 0°C (32°F) 4.40 to 5.35 kΩ 5°C (41°F) 3.40 to 4.15 kΩ 10°C (50°F) 2.70 to 3.25 kΩ 15°C (59°F) 2.14 to 2.58 kΩ 20°C (68°F) 1.71 to 2.05 kΩ 25°C (77°F) 1.38 to 1.64 kΩ 30°C (86°F) 1.11 to 1.32 kΩ
- NOTICE:
- Even slightly touching the sensor may change the resistance value. Be sure to hold the connector of the sensor.
- When measuring, the sensor temperature must be the same as the ambient temperature.
- HINT:
- As the temperature increases, the resistance decreases (refer to the graph).
Text in Illustration *a Component without harness connected
(No. 1 Cooler Thermistor (Front Evaporator Temperature Sensor))*b Sensor Part *c Resistance kΩ *d Temperature °C (°F)