Dtc 43 Air Outlet Damper Control Servo Motor Circuit
DESCRIPTION
WIRING DIAGRAM
INSPECTION PROCEDURE
PERFORM ACTUATOR CHECK
CHECK HARNESS AND CONNECTOR (MODE DAMPER SERVO - AIR CONDITIONING AMPLIFIER)
REPLACE MODE DAMPER SERVO SUB-ASSEMBLY
DTC 43 Air Outlet Damper Control Servo Motor Circuit |
DESCRIPTION
The mode damper servo sub-assembly sends pulse signals to inform the air conditioning amplifier assembly of the mode damper position. The air conditioning amplifier assembly activates the motor (normal or reverse) based on the signals to move the mode damper to any position, which controls the mode changes.- HINT:
- This DTC is also output if the mode damper and damper link are malfunctioning or unable to move properly. When this DTC is output, confirm that the mechanical parts of the mode damper and damper link are not defective or damaged.
DTC Code
| Detection Item
| Trouble Area
|
43
| The mode damper position does not change when the air conditioning amplifier assembly operates the mode damper servo sub-assembly.
| - Mode damper servo sub-assembly
- Air conditioning amplifier assembly
- Harness or connector
|
WIRING DIAGRAM
INSPECTION PROCEDURE
Warm up the engine.
Enter actuator check mode (HILUX_TGN26 RM000003R7I00IX.html).
Place your hand in front of a vent and check that the mode damper position changes according to the display code.
Display Code
| Mode Damper Position
|
0
| FACE
|
1
| FACE
|
2
| FACE
|
3
| FACE
|
4
| FACE
|
5
| BI-LEVEL
|
6
| FOOT
|
7
| FOOT
|
8
| FOOT/DEF
|
9
| DEF
|
- OK:
- Mode damper position changes in accordance with each display code.
- HINT:
- The progression through the steps of the actuator check can be changed from automatic to manual by pressing the front DEF switch.
ResultResult
| Proceed to
|
OK (When troubleshooting according to problem symptoms table.)
| A
|
OK (When troubleshooting according to DTC.)
| B
|
NG
| C
|
2.CHECK HARNESS AND CONNECTOR (MODE DAMPER SERVO - AIR CONDITIONING AMPLIFIER) |
Disconnect the G79 mode damper servo sub-assembly connector.
Disconnect the G94 and G95 air conditioning amplifier assembly connectors.
Measure the resistance according to the value(s) in the table below.
- Standard Resistance:
Tester Connection
| Condition
| Specified Condition
|
G79-4 (DEF) - G94-4 (AOD)
| Always
| Below 1 Ω
|
G79-5 (FACE) - G94-3 (AOF)
|
G79-2 (FDEF) - G95-26 (POA)
|
G79-3 (HEAT) - G95-25 (POB)
|
G79-1 (SG) - G95-11 (SG-2)
|
G79-4 (DEF) - Body ground
| Always
| 10 kΩ or higher
|
G79-5 (FACE) - Body ground
|
G79-2 (FDEF) - Body ground
|
G79-3 (HEAT) - Body ground
|
G79-1 (SG) - Body ground
|
| REPAIR OR REPLACE HARNESS OR CONNECTOR |
|
|
3.REPLACE MODE DAMPER SERVO SUB-ASSEMBLY |
Temporally replace the mode damper servo sub-assembly with a new or normally functioning one (HILUX_TGN26 RM0000012JQ01HX.html).
Check the mode damper operates normally.
- OK:
- Mode damper operates normally.
OK |
|
|
|
END (MODE DAMPER SERVO IS DEFECTIVE) |
|