Dtc B1423/23 Pressure Sensor Circuit

Vehicle Interior. Yaris. Ncp93, 131
Heating Air Conditioning. Yaris. Ncp93, 131

DESCRIPTION

WIRING DIAGRAM

INSPECTION PROCEDURE

CHECK REFRIGERANT

READ VALUE USING TECHSTREAM (REGULATOR PRESSURE SENSOR)

CHECK HARNESS AND CONNECTOR (PRESSURE SENSOR - AIR CONDITIONING AMPLIFIER)

INSPECT AIR CONDITIONING AMPLIFIER

INSPECT AIR CONDITIONING PRESSURE SENSOR

DTC B1423/23 Pressure Sensor Circuit


DESCRIPTION

This DTC is output when the refrigerant pressure is either extremely low (0.19 Mpa [2.0 kgf/cm2, 28 psi] or less) or extremely high (3.14 Mpa [32.0 kgf/cm2, 455 psi] or more). The pressure sensor, which is installed on the pipe of the high pressure side, detects the refrigerant pressure and sends a refrigerant pressure signal to the air conditioning amplifier. The air conditioning amplifier determines the pressure from the signals in accordance with the sensor characteristics, and controls the compressor.

DTC No.
DTC Detection Condition
Trouble Area
B1423/23
Open or short in pressure sensor circuit
  1. Air conditioning pressure sensor
  2. Harness and connector between air conditioning pressure sensor and air conditioning amplifier
  3. Air conditioning amplifier

WIRING DIAGRAM


Yaris. Ncp93, 131.Heating Air Conditioning.Air Conditioning System (For Sedan).
Dtc
  B1423/23  Pressure Sensor Circuit


INSPECTION PROCEDURE

1.CHECK REFRIGERANT
  1. Check the sight glass of the cooler unit refrigerant liquid pipe.

    1. Prepare the vehicle in accordance with the chart below.

      Item
      Condition
      Vehicle Doors
      Fully open
      Temperature Setting
      MAX COLD
      Blower Speed
      HI
      A/C Switch
      ON
    2. Compare the sight glass to the following chart.

      Item
      Symptom
      Amount of Refrigerant
      Corrective Procedures
      1
      Bubbles visible
      Insufficient*
      (1) Check for gas leakage and repair if necessary
      (2) Add refrigerant until bubbles disappear
      2
      No bubbles visible
      Empty, insufficient or too much
      Refer to items 3 and 4
      3
      No temperature difference between compressor inlet and outlet
      Empty or nearly empty
      (1) Check for gas leakage with gas leak detector and repair if necessary
      (2) Add refrigerant until bubbles disappear
      4
      Considerable temperature difference between compressor inlet and outlet
      Correct or too much
      Refer to items 5 and 6
      5
      Immediately after A/C turned OFF, refrigerant becomes clear
      Too much
      (1) Drain or discharge refrigerant
      (2) Bleed air and supply proper amount of purified refrigerant
      6
      Immediately after A/C turned OFF, refrigerant foams and then becomes clear
      Correct
      -
      HINT:
      *: If the ambient temperature is higher than usual but cooling is sufficient, bubbles in the sight glass are permissible.


NG
CHARGE REFRIGERANT (YARIS_NCP93 RM000000R5701SX.html)
OK


2.READ VALUE USING TECHSTREAM (REGULATOR PRESSURE SENSOR)
  1. Warm up the engine.

  1. Turn the ignition switch to OFF.

  1. Connect the Techstream to the DLC3.

  1. Turn the ignition switch ON and turn the Techstream main switch ON.

  1. Turn the ignition switch to ON.

  1. Turn the tester on.

  1. Select the following menus: Body Electrical / Air Conditioner / Data List /

  1. According to the display on tester, read the "Data List".

    Data List / Air Conditioner:

    Tester Display
    Measure Item/Range
    Normal Condition
    Diagnostic Note
    Regulator Pressure Sensor
    Regulator Pressure Sensor /
    Min.: 0 kgf / cm 2G,
    Max.: 38.25 kgf / cm 2G
    Actual regulator pressure is displayed
    -
    OK:
    The display is as specified in the normal condition column.

    Result:

    Result
    Proceed to
    NG
    A
    OK (When troubleshooting according to PROBLEM SYMPTOMS TABLE)
    B
    OK (When troubleshooting according to the DTC)
    C


B
PROCEED TO NEXT CIRCUIT INSPECTION SHOWN IN PROBLEM SYMPTOMS TABLE (YARIS_NCP93 RM000001CXV007X.html)

C
REPLACE AIR CONDITIONING AMPLIFIER (YARIS_NCP93 RM000001HO100MX.html)
A


3.CHECK HARNESS AND CONNECTOR (PRESSURE SENSOR - AIR CONDITIONING AMPLIFIER)
Yaris. Ncp93, 131.Heating Air Conditioning.Air Conditioning System (For Sedan).
Dtc
  B1423/23  Pressure Sensor Circuit
  1. Disconnect the A3 air conditioning pressure sensor connector.

  1. Disconnect the E8 air conditioning amplifier connector.

  1. Measure the resistance.

    Standard resistance:
    Tester Connection
    Specified Condition
    A3-1 (-) - E8-11 (SG-1)
    Below 1 Ω
    A3-2 (PR) - E8-6 (PRE)
    Below 1 Ω
    A3-3 (+) - E8-1 (S5-3)
    Below 1 Ω
    A3-1 (-) - Body ground
    10 kΩ or higher
    A3-2 (PR) - Body ground
    10 kΩ or higher
    A3-3 (+) - Body ground
    10 kΩ or higher
  1. Reconnect the air conditioning pressure sensor connector.

  1. Reconnect the air conditioning amplifier connector.



NG
REPAIR OR REPLACE HARNESS OR CONNECTOR
OK


4.INSPECT AIR CONDITIONING AMPLIFIER
Yaris. Ncp93, 131.Heating Air Conditioning.Air Conditioning System (For Sedan).
Dtc
  B1423/23  Pressure Sensor Circuit
  1. Remove the air conditioning amplifier with its connectors still connected.

  1. Measure the resistance.

    Standard resistance:
    Tester Connection
    Specified Condition
    E8-11 (SG-1) - E8-12 (GND)
    Below 1 Ω
  1. Turn the ignition switch ON.

  1. Measure the voltage.

    Standard voltage:
    Tester Connection
    Specified Condition
    E8-1 (S5-3) - E8-11 (SG-1)
    4.5 to 5.5 V
  1. Reinstall the air conditioning amplifier.



NG
REPLACE AIR CONDITIONING AMPLIFIER (YARIS_NCP93 RM000001HO100MX.html)
OK


5.INSPECT AIR CONDITIONING PRESSURE SENSOR
Yaris. Ncp93, 131.Heating Air Conditioning.Air Conditioning System (For Sedan).
Dtc
  B1423/23  Pressure Sensor Circuit
  1. Remove the air conditioning amplifier with its connectors still connected.

  1. Set the manifold gauge.

  1. Warm up the engine.

  1. Turn the A/C switch ON.

  1. Measure the voltage.

    Standard voltage:
    Tester Connection
    Refrigerant Pressure
    Specified Condition
    E8-6 (PRE) - E8-11 (SG-1)
    0.196 to 3.14 MPa
    (2.0 to 32 kgf/cm2)
    0.76 to 4.74 V
  1. Reinstall the air conditioning amplifier.



NG
REPLACE LIQUID TUBE SUB-ASSEMBLY A (AIR CONDITIONING PRESSURE SENSOR)
OK

REPLACE AIR CONDITIONING AMPLIFIER (YARIS_NCP93 RM000001HO100MX.html)