Refrigerant -- On-Vehicle Inspection |
1. INSPECT REFRIGERANT PRESSURE WITH MANIFOLD GAUGE SET |
This method uses a manifold gauge set to locate problem areas. Read the manifold gauge pressure when these conditions are established.
Test conditions:- Temperature at the air inlet with the switch set at RECIRC is 30 to 35°C (86 to 95°F).
- Engine is running at 1500 rpm.
- All doors are fully open.
- Blower speed control switch is at HI.
- A/C switch is on.
Normally functioning refrigeration system
- Gauge Reading:
Pressure Side Refrigerant Volume Low 0.15 to 0.25 MPa (1.5 to 2.5 kgf/cm2) High 1.37 to 1.57 MPa (14 to 16 kgf/cm2)
The A/C system periodically changes between normal and improper function due to moisture in the refrigerant system.
Symptoms Probable Cause Diagnosis Corrective Actions During operation, pressure on low pressure side cycles between normal and vacuum Moisture in refrigeration system freezes at expansion valve orifice, causing temporary stop of cycle. However, when melted, normal state is restored. - Dryer is overly saturated
- Moisture in refrigeration system freezes at expansion valve orifice and blocks refrigerant circulation1. Replace cooler dryer
2. Remove moisture from cycle by repeatedly evacuating air
3. Supply appropriate volume of new refrigerantThe A/C system does not function effectively due to insufficient refrigerant.
Symptoms Probable Cause Diagnosis Corrective Actions - Pressure low on both low and high pressure sides
- Cooling performance insufficientGas leakage from refrigeration system - Insufficient refrigerant
- Refrigerant leakage1. Check for gas leakage and repair if necessary
2. Supply appropriate volume of new refrigerant
3. If indicated pressure value close to 0 when connected to gauge, create vacuum after inspecting and repairing the location of leakageThe A/C system does not function effectively due to poor circulation of the refrigerant.
Symptoms Probable Cause Diagnosis Corrective Actions - Pressure low on both low and high pressure sides
- Frost exists on piping from condenser to A/C unitRefrigerant flow obstructed by dirt in condenser Condenser clogged Replace condenser The A/C system does not function or functions intermittently because the refrigerant does not circulate.
Symptoms Probable Cause Diagnosis Corrective Actions - Vacuum indicated on low pressure side, and extremely low pressure indicated on high pressure side
- Frost or condensation seen on piping on both sides of condenser or expansion valve- Refrigerant flow obstructed by moisture or dirt in refrigeration system
- Refrigerant flow obstructed by gas leakage from expansion valveRefrigerant does not circulate 1. Check expansion valve refrigerant
2. Clean expansion valve by blowing air
3. Replace condenser
4. Evacuate air and charge appropriate volume of new refrigerant
5. For gas leakage from expansion valve, replace expansion valveThe A/C system does not function effectively due to overcharged refrigerant or insufficient cooling of the condenser.
Symptoms Probable Cause Diagnosis Corrective Actions Pressure extremely high on both low and high-pressure sides - Excessive refrigerant
- Cooling performance of condenser insufficient- Condenser is dirty
- Condenser fan motor is malfunctioning
- Excessive refrigerant1. Clean condenser
2. Check condenser fan motor operation
3. If 1 and 2 normal, check the amount of refrigerant and supply appropriate volume of refrigerantThe A/C system does not function due to air in the refrigeration system.
- CAUTION:
- The low-pressure piping may be very hot and cause serious burns.
Symptoms Probable Cause Diagnosis Corrective Actions - Pressure extremely high on both low and high-pressure sides
- Low-pressure piping is too hot to touchAir in refrigeration system - Air in refrigeration system
- Vacuum purging insufficient1. Check if compressor oil is dirty or insufficient
2. Evacuate air and charge new refrigerantThe A/C system does not function effectively due to an expansion valve malfunction.
Symptoms Probable Cause Diagnosis Corrective Actions - Pressure extremely high on both low and high-pressure sides
- Frost or condensation on piping on low-pressure sideProblem with expansion valve - Excessive refrigerant in low pressure piping
- Expansion valve too wide openReplace expansion valve The A/C system does not function due to a defective compressor.
Symptoms Probable Cause Diagnosis Corrective Actions - Pressure extremely high on both low and high-pressure sides
- Pressure extremely low on high pressure sideInternal leakage in compressor - Compression failure
- Leakage from damaged valve or broken sliding partsRepair or replace compressor
- Temperature at the air inlet with the switch set at RECIRC is 30 to 35°C (86 to 95°F).