Ambient Temperature Sensor (For Automatic Air Conditioning System) Inspection


  1. INSPECT AMBIENT TEMPERATURE SENSOR

Ambient Temperature Sensor (For Automatic Air Conditioning System) -- Inspection



1. INSPECT AMBIENT TEMPERATURE SENSOR


Toyota Fortuner. Ggn50, 60 Kun51, 61 Tgn51 Lan50.Air Conditioning.Ambient Temperature Sensor (For Automatic Air Conditioning System).Ambient Temperature Sensor (For Automatic Air Conditioning System)  Inspection
  1. Measure the resistance according to the value(s) in the table below.

    Standard Resistance:
    Tester Connection
    Condition
    Specified Condition
    1 - 2
    10°C (50°F)
    3.00 to 3.73 kΩ
    15°C (59°F)
    2.45 to 2.88 kΩ
    20°C (68°F)
    1.95 to 2.30 kΩ
    25°C (77°F)
    1.60 to 1.80 kΩ
    30°C (86°F)
    1.28 to 1.47 kΩ
    35°C (95°F)
    1.00 to 1.22 kΩ
    40°C (104°F)
    0.80 to 1.00 kΩ
    45°C (113°F)
    0.65 to 0.85 kΩ
    50°C (122°F)
    0.50 to 0.70 kΩ
    55°C (131°F)
    0.44 to 0.60 kΩ
    60°C (140°F)
    0.36 to 0.50 kΩ
    If the result is not as specified, replace the ambient temperature sensor.
    NOTICE:
    1. Touching the sensor even slightly may change the resistance value. Hold the connector of the sensor.
    1. When measuring the resistance, the sensor temperature must be the same as the ambient temperature.
    HINT:
    As the temperature increases, the resistance decreases (refer to the graph).