Vehicle Interior. Land Cruiser. Urj200, 202 Grj200 Vdj200
Heating Air Conditioning. Land Cruiser. Urj200, 202 Grj200 Vdj200
Air Conditioning System (For Manual Air Conditioning System) -- Data List / Active Test |
- HINT:
- Using the GTS to read the Data List allows the values or states of switches, sensors, actuators and other items to be read without removing any parts. This non-intrusive inspection can be very useful because intermittent conditions or signals may be discovered before parts or wiring is disturbed. Reading the Data List information early in troubleshooting is one way to save diagnostic time.
- NOTICE:
- In the table below, the values listed under "Normal Condition" are reference values. Do not depend solely on these reference values when deciding whether a part is faulty or not.
DATA LIST |
Connect the GTS to the DLC3.
Turn the ignition switch to ON.
Turn the GTS on.
Enter the following menus: Body Electrical / Air Conditioner / Data List.
Enter the following menus: Powertrain / Engine and ECT / Data List.
According to the display on the GTS, read the Data List.
Air Conditioner Tester Display Measurement Item/Range Normal Condition Diagnostic Note Ambient Temp Sensor Cooler thermistor (ambient temperature sensor) / Min.: -23.3°C (-9.94°F), Max.: 65.95°C (150.71°F) Actual ambient temperature displayed Thermistor assembly (ambient temperature sensor) system malfunction: - Open in the circuit: -23.3°C (-9.94°F)
- Short in the circuit: 65.95°C (150.71°F)
Adjusted Ambient Temp Adjusted ambient temperature /Min.: -30.8°C (-23.44°F), Max.: 50.8°C (123.44°F) Adjusted ambient temperature displayed Air conditioning amplifier assembly Evaporator Fin Thermistor No. 1 cooler thermistor (evaporator temperature sensor) / Min.: -29.7°C (-21.46°F), Max.: 59.55°C (139.19°F) Actual evaporator temperature displayed No. 1 cooler thermistor (evaporator temperature sensor) system malfunction: - Open in the circuit: -29.7°C (-21.46°F)
- Short in the circuit: 59.55°C (139.19°F)
Engine Coolant Temp Engine coolant temperature / Min.: 1.3°C (34.34°F), Max.: 90.55°C (194.99°F) Actual engine coolant temperature displayed while engine warmed up - SFI system malfunction
- CAN communication system malfunction
Blower Motor Speed Level Blower with fan motor sub-assembly speed level / Min.: 0 level, Max.: 31 level Displayed speed level increases in range between 0 and 31 as blower with fan motor subassembly speed increases Displayed speed level increases in range between 0 and 31 as blower with fan motor subassembly speed increases Regulator Pressure Sensor Air conditioner pressure sensor / Min.: 0.4566 MPa, Max.: 3.2943 MPa Actual refrigerant pressure displayed - Air conditioning system (leaks, blocked)
- Air conditioner pressure sensor system malfunction
Air Mix Servo Targ Pulse(D) Air mix damper servo motor target pulse / Min.: 128, Max.:383 for LHD:- MAX COLD: 218 (pulse)
- MAX HOT: 136 (pulse)
for RHD:- MAX COLD: 136 (pulse)
- MAX HOT: 218 (pulse)
- Displayed between 136 and 218 pulse
- Air mix damper servo motor system malfunction
Air Mix Servo Actual Pulse(D) Air mix damper servo motor actual pulse / Min.: 128, Max.:383 for LHD:- MAX COLD: 218 (pulse)
- MAX HOT: 136 (pulse)
for RHD:- MAX COLD: 136 (pulse)
- MAX HOT: 218 (pulse)
- Displayed between 136 and 218 pulse
- Air mix damper servo motor system malfunction
Air Outlet Servo Pulse (D) Mode damper servo motor target pulse / Min.: 128, Max.:383 - FACE1: 245 (pulse)
- FACE2: 237 (pulse)
- B/L1: 221 (pulse)
- B/L2: 209 (pulse)
- FOOT-O: 199 (pulse)
- FOOT-D: 180 (pulse)
- FOOT-R: 169 (pulse)
- FOOT-F: 169 (pulse)
- F/D: 146 (pulse)
- DEF: 134 (pulse)
- Displayed between 134 and 245 pulse
- Mode damper servo motor system malfunction
Air Outlet Servo Actu Pulse(D) Mode damper servo motor actual pulse / Min.: 128, Max.:383 - FACE1: 245 (pulse)
- FACE2: 237 (pulse)
- B/L1: 221 (pulse)
- B/L2: 209 (pulse)
- FOOT-O: 199 (pulse)
- FOOT-D: 180 (pulse)
- FOOT-R: 169 (pulse)
- FOOT-F: 169 (pulse)
- F/D: 146 (pulse)
- DEF: 134 (pulse)
- Displayed between 136 and 245 pulse
- Mode damper servo motor system malfunction
Air Inlet Damper Targ Pulse Mode damper servo motor (REC/FRS) target pulse / Min.: 128, Max.:383 for LHD:- RECIRCULATION: 165 (pulse)
- FRESH: 137 (pulse)
for RHD:- RECIRCULATION: 137 (pulse)
- FRESH: 165 (pulse)
- Displayed between 137 and 165 pulse
- Mode damper servo motor (REC/FRS) system malfunction
Air Inlet Damper Actual Pulse Mode damper servo motor (REC/FRS) actual pulse / Min.: 128, Max.:383 for LHD:- RECIRCULATION: 165 (pulse)
- FRESH: 137 (pulse)
for RHD:- RECIRCULATION: 137 (pulse)
- FRESH: 165 (pulse)
- Displayed between 137 and 165 pulse
- Mode damper servo motor (REC/FRS) system malfunction
Cool Air Bypass Pulse Cool air bypass damper servo motor target pulse / Min.: 128, Max.:383 - Shut: 134 (pulse)
- Open: 185 (pulse)
- Displayed between 134 and 185 pulse
- Cool air bypass damper servo motor) system malfunction
Cool Air Bypass Actual Pulse Cool air bypass damper servo motor actual pulse / Min.: 128, Max.:383 - Shut: 134 (pulse)
- Open: 185 (pulse)
- Displayed between 134 and 185 pulse
- Cool air bypass damper servo motor) system malfunction
Electric Heater Count Electric heater count /
Min.: 0, Max.: 3Maximum possible operation of electric heater displayed PTC heater system malfunction Electric Heater Active Level Actual electric heater operation level Actual operation level of electric heater displayed PTC heater system malfunction Refrigerant Shortage Check Refrigerant gas volume check / ON, OFF Customized value displayed - IDLE UP/PWR HEAT Switch Idle up switch / ON, OFF ON: Idle up switch on
OFF: Idle up switch offw/ Viscous Heater Refrigerant Gas Type Refrigerant gas type / R134a or 1234yf Refrigerant gas type displayed - Number of Trouble Codes Number of trouble codes / Min.: 0, Max.: 255 Number of DTCs displayed - Engine Tester Display Measurement Item/Range Normal Condition Diagnostic Note A/C Signal A/C signal / ON or OFF ON: A/C Switch on
OFF: A/C Switch off- - Open in the circuit: -23.3°C (-9.94°F)
ACTIVE TEST |
- HINT:
- Using the GTS to perform Active Tests allows relays, VSVs, actuators and other items to be operated without removing any parts. This non-intrusive functional inspection can be very useful because intermittent operation may be discovered before parts or wiring is disturbed. Performing Active Tests early in troubleshooting is one way to save diagnostic time. Data List information can be displayed while performing Active Tests.
Connect the GTS to the DLC3.
Turn the ignition switch to ON.
Turn the GTS on.
Enter the following menus: Body Electrical / Air Conditioner / Active Test.
According to the display on the GTS, perform the Active Test.
Air Conditioner Tester Display Test Part Control Range Diagnostic Note Blower Motor Blower motor Min.: 0, Max.: 31 - Heater Active Level Heater active level Min.: 0, Max.: 3 - Magnetic Clutch Relay Magnetic clutch relay ON or OFF - Air Mix Servo Targ Pulse(D) Air mix damper servo motor pulse Min.: 128, Max.: 383 Operates between 136 to 218 Air Outlet Servo Pulse (D) Mode damper servo motor Pulse Min.: 128, Max.: 383 Operates between 136 to 245 Air Inlet Damper Targ Pulse Mode damper servo motor (REC/FRS) pulse Min.: 128, Max.: 383 Operates between 137 to 165 Cool Air Bypass Pulse Cool air bypass damper servo motor pulse Min.: 128, Max.: 383 Operates between 134 to 185