Vehicle Interior. Corolla. Zre142 Aze141
Heating Air Conditioning. Corolla. Zre142 Aze141
Refrigerant -- On-Vehicle Inspection |
1. INSPECT REFRIGERANT PRESSURE WITH MANIFOLD GAUGE SET |
- HINT:
- This is a method where a manifold gauge set is used to help locate the problem.
Read the manifold gauge pressure when the following conditions are established.
Test conditions:- Temperature at the air inlet with the switch set at RECIRC is 30 to 35°C (86 to 95°F).
- Engine is running at 1500 rpm.
- Blower speed control switch is at "HI".
- Temperature control dial is at "COOL".
- A/C switch is ON.
- Doors are fully open.
Normally functioning refrigeration system
Gauge Reading Pressure Side Refrigerant Volume Low 0.15 to 0.25 MPa (1.5 to 2.5 kgf/cm2, 21 to 36 psi) High 1.37 to 1.57 MPa (13.9 to 16.0 kgf/cm2, 198 to 227 psi) Moisture is present in refrigeration system.
Symptom Probable Cause Diagnosis Corrective Action During operation, pressure on low pressure side cycles between normal and vacuum - Moisture in the A/C system will freeze at the expansion valve orifice, causing the refrigeration cycle to temporarily stop
- After the system stops, and warms up again, the ice will melt and normal operation will be temporarily restored
- Cooler dryer (integrated into the condenser tank) in oversaturated state
- Moisture in the refrigeration system freezes at the expansion valve orifice and blocks circulation of refrigerant
- Replace the cooler dryer
- Remove moisture in the system by repeatedly evacuating air
- Supply a proper amount of new refrigerant
- Moisture in the A/C system will freeze at the expansion valve orifice, causing the refrigeration cycle to temporarily stop
Insufficient cooling
Symptom Probable Cause Diagnosis Corrective Action - Pressure is low on both low and high pressure sides
- Insufficient cooling performance
Gas leakage from the refrigeration system - Insufficient refrigerant
- Refrigerant leaking
- Check for gas leaks and repair if necessary
- Supply a proper amount of new refrigerant
- If the gauge indicates a pressure of close to 0, then it will be necessary to evacuate the system after repairing the leak
- Pressure is low on both low and high pressure sides
Poor circulation of refrigerant
Symptom Probable Cause Diagnosis Corrective Action - Pressure is low on both low and high pressure sides
- Frost exists on pipe from condenser to unit
Refrigerant flow is obstructed by dirt inside the pipes of the condenser core Receiver is clogged Replace the condenser - Pressure is low on both low and high pressure sides
Refrigerant does not circulate.
Symptom Probable Cause Diagnosis Corrective Action - Vacuum is indicated on low pressure side and very low pressure is indicated on high pressure side
- Frost or condensation is seen on piping on both sides of receiver/drier or expansion valve
- Refrigerant flow is obstructed by moisture or dirt in the refrigeration system
- Refrigerant flow is obstructed by gas leaking internally through the expansion valve
Refrigerant does not circulate - Check the expansion valve
- Replace the expansion valve
- Replace the condenser
- Evacuate air and supply a proper amount of new refrigerant
- For internal gas leak at the expansion valve, replace the expansion valve
- Vacuum is indicated on low pressure side and very low pressure is indicated on high pressure side
Refrigerant is overcharged or cooling effectiveness of the condenser is insufficient.
Symptom Probable Cause Diagnosis Corrective Action Pressure is too high on both low and high pressure sides - Unable to develop sufficient performance due to an excessive use of refrigeration system
- Cooling effectiveness of the condenser is insufficient
- Excessive refrigerant in cycle → excessive refrigerant was added during recharging
- Condenser cooling effectiveness is insufficient → condenser fins are clogged at the cooling fan
- Clean the condenser
- Check the operation of the condenser cooling fan
- If 1 and 2 are normal state, check the amount of refrigerant and supply the proper amount of refrigerant
- Unable to develop sufficient performance due to an excessive use of refrigeration system
Air is present in the refrigeration system.
Symptom Probable Cause Diagnosis Corrective Action - Pressure is too high on both low and high pressure sides
- The low pressure piping is too hot to touch
Air in the system - Air present in the refrigeration system
- Insufficient vacuum purging
- Check compressor oil to see if it is dirty or insufficient
- Evacuate the system and recharge it with new or purified refrigerant
- Pressure is too high on both low and high pressure sides
Expansion valve malfunction
Symptom Probable Cause Diagnosis Corrective Action - Pressure is too high on both low and high pressure sides
- Frost or a large amount of condensation on piping on low pressure side
Expansion valve may be sticking - Excessive refrigerant in low pressure piping
- Expansion valve opened too wide
Check expansion valve - Pressure is too high on both low and high pressure sides
Insufficient compressor compression
Gauge readings (Reference)Symptom Probable Cause Diagnosis Corrective Action - Pressure is too high both on low and high pressure sides
- Pressure is too low on high pressure side
Internal leak in the compressor - Low compression
- Leak from a damaged valve, or parts may be broken
Replace the compressor - Pressure is too high both on low and high pressure sides
- Temperature at the air inlet with the switch set at RECIRC is 30 to 35°C (86 to 95°F).