Air Conditioning System (For Automatic Air Conditioning System) -- Data List / Active Test |
Data List |
Connect the Techstream to the DLC3.
Turn the ignition switch to ON.
Turn the Techstream on.
Enter the following menus: Body Electrical / Air Conditioner / Data List.
Check the value(s) by referring to the table below.
Air Conditioner Tester Display Measurement Item/Range Normal Condition Diagnostic Note Room Temperature Sensor
(Room Temp)Room temperature sensor / Min.: -6.5°C (20.3°F), Max.: 57.25°C (135.05°F) Actual cabin temperature displayed - Ambient Temp Sensor
(Ambi Temp Sens)Ambient temperature sensor / Min.: -23.3°C (-9.94°F), Max.: 65.95°C (150.71°F) Actual ambient temperature displayed - Adjusted Ambient Temp
(Ambi Temp)Adjusted ambient temperature / Min.: -30.8°C (-23.44°F), Max.: 50.8°C (123.44°F) - - Evaporator Fin Thermistor
(Evap Fin Temp)Evaporator fin temperature / Min.: -29.7°C (-21.46°F), Max.: 59.55°C (139.19°F) Actual evaporator temperature displayed - Solar Sensor (D side)
(Solar Sens-D)Driver side solar sensor / Min.: 0, Max.: 255 Driver side solar sensor value increases as brightness increases - Engine Coolant Temp
(Coolant Temp)Engine coolant temperature / Min.: 1.3°C (34.34°F), Max.: 90.55°C (194.99°F) Actual engine coolant temperature displayed while engine is warmed up - Set Temperature (D side)
(Set Temp-D)Driver side set temperature / Min.: 18°C (65°F), Max.: 32°C (85°F) Driver side set temperature displayed - Blower Motor Speed Level
(Blower Level)Blower motor speed level / Min.: 0, Max.: 31 Increases in the range between 0 and 31 as the blower motor speed increases - Regulator Pressure Sensor
(Reg Press Sens)Regulator pressure sensor / Min.: -0.45668 MPaG, Max.: 3.29437 MPaG Actual refrigerant pressure displayed - Regulator Control Current
(Reg Ctrl Currnt)Compressor variable output current / Min.: 0 A, Max.: 0.997 A - - Air Mix Servo Targ Pulse(D)
(Air Mix Pulse-D)Driver side air mix servo motor target pulse / Min.: 0, Max.: 255 MAX. COLD: 93 (pulse)
MAX. HOT: 6 (pulse)- Air Outlet Servo Pulse (D)
(Air Out Pulse-D)Driver side air outlet servo motor target pulse / Min.: 0, Max.: 255 FACE: 47 (pulse)
B/L: 37 (pulse)
FOOT: 17 (pulse)
FOOT/DEF: 9 (pulse)
DEF: 5 (pulse)- Air Inlet Damper Targ Pulse
(A/I Damp Targ Pls)Air inlet damper target pulse / Min.: 0, Max.: 255 - RECIRCULATION: 19 (pulse)
- FRESH: 7 (pulse)
- Electric Heater Count*2
(Heater Count)Number of electric heaters operating / Min.: 0, Max.: 3 - - Shift Set Temperature
(Set Temp Shift)Shift set temperature / 2 C incr, 1 C incr, Normal, 1 C decr, 2 C decr, Customized value displayed - Air Inlet Mode
(Air Inlet Mode)Air inlet mode / Auto or Normal Customized value displayed - Compressor/DEF Mode
(Comprs/DEF Oper)Compressor/DEF mode / Link or Normal Customized value displayed - Evaporator Control
(Evap Ctrl)Evaporator Control / Auto or Normal Customized value displayed - Foot/DEF Auto Blow Up
(Auto blow Up)Foot/DEF auto blow speed increase/ ON or OFF Customized value displayed - Foot/DEF Auto Mode
(Foot/DEF Mode)Foot/DEF auto mode / ON or OFF Customized value displayed - Flow Sensor*1
(Flow Sens)A/C flow sensor / Min.: 0 V, Max.: 5 V A/C on, Blower switch HI: 0.7 to 3.8 V
A/C off, Blower switch off: 3.8 to 4.2 VA/C flow sensor is malfunctioning when a constant value below 0.7 V or higher than 4.2 V is displayed continuously for more than 4 seconds. A/C Cutoff Signal
(A/C Cutoff)A/C control cutoff signal / OFF or ON A/C switch on: OFF
A/C switch off: ON- Number of Trouble Codes
(#Codes)Number of trouble codes / Min.: 0, Max.: 255 Number of DTCs will be displayed - - *1: for 2ZR-FE
- *2: w/ PTC Heater Assembly
- RECIRCULATION: 19 (pulse)
Active Test |
- HINT:
- Using the Techstream to perform Active Tests allows the relay actuator and other items to be operated without removing any parts. This non-intrusive functional inspection can be very useful because intermittent operation may be discovered before parts or wiring is disturbed. Performing Active Test early in troubleshooting is one way to save diagnostic time. Data List information can be displayed while performing Active Test.
Connect the Techstream to the DLC3.
Turn the ignition switch to ON.
Turn the Techstream on.
Enter the following menus: Body Electrical / Air Conditioner / Active Test.
Check the operation by referring to the table below.
Air Conditioner Tester Display Test Part Control Range Diagnostic Note Blower Motor
(Blower Motor)Blower motor Min.: 0, Max.: 31 - Magnetic Clutch Relay
(A/C Mag Clutch)A/C system operation OFF, ON - Defogger Relay (Rear)
(Defogger Rly-R)Defogger relay (Rear) OFF, ON - Heater Active Level*1
(Heater Level)Heater active level Min.: 0, Max.: 3 - Air Mix Servo Targ Pulse(D)
(Air Mix Pulse-D)Driver side air mix servo motor pulse Min.: 0, Max.: 255 - Air Outlet Servo Pulse (D)
(Air Out Pulse-D)Driver side air outlet servo motor pulse Min.: 0, Max.: 255 - Air Inlet Damper Targ Pulse
(A/I Damp Targ Pls)Air inlet damper target pulse Min.: 0, Max.: 255 - - *1: w/ PTC Heater Assembly
- *1: w/ PTC Heater Assembly